Poor effluent quality

Hamworthy Super Trident ST6A, biological (aerobic) sewage treatment plant, imo mepc.2(vi)

Possible cause

Lack of oxygen, killed bacteria by disinfectant cleaners, sludge not returning, too much flushing water

What to do

Check compressors, filters and valves; stop disinfectant cleaners; set air-lifts; fix leaking flush valves

Manufacturer's manual, p. 56