Air gauge 0.2 bar above normal / relief valve blowing
Hamworthy Super Trident ST6A, biološki uređaj za obradu otpadnih voda, imo mepc.2(vi)
Mogući uzrok
Clogged diffuser elements or dirty filters
Što učiniti
Priručnik proizvođača, str. 59Replace diffuser elements and clean filter cartridges
Ostali kvarovi Hamworthy Super Trident ST6A
Tank overflow / high level alarmDischarge pump failure, pipe blockage or excessive inflow (leaking WC flush valves)Bad smell from the unitAnaerobic tank: compressor, air-lifts or diffusers not working, or too much sludgePoor effluent qualityLack of oxygen, killed bacteria by disinfectant cleaners, sludge not returning, too much flushing waterScum on the settling tankSkimmer or air-lifts not workingFoaming in the aeration tank and ventToo much cleaning agentDischarge pump gives no flowClosed valves, blocked suction, air leaks or loops in suction pipeReduced or irregular pump dischargeChoked impeller, valve or non-return valve partly closed