10.2.1 Emergency generator
CoreChemicalLNGLPGOilAsked to: Chief Officer, 2nd / 3rd Officer, Chief Engineer, Engineer officersWhere: Exterior DecksOnly if it applies to the ship
Can the officers explain how to start the emergency generator and supply the emergency switchboard, and are there records proving it has been tested as the company procedure requires?
In one lineStarts automatically on blackout and connects in 45 s; I can start it manually by both means; weekly and on-load tests are recorded.
How to answer
- Explain the automatic start: on loss of main switchboard voltage the generator starts and connects to the emergency switchboard (SOLAS allows 45 seconds)
- Describe manual start with the primary and the secondary starting means, and how you put it on the board manually if needed
- Explain how the fuel tank quick closing valve is operated and reset, and how it is tested without starving a running engine
- State the test routine: weekly run, periodic on-load test, and blackout simulation per company procedure, all logged
- Mention fuel capacity for at least 18 hours of operation (cargo ships) and that the tank is kept topped up
What the inspector looks for
- Officers can start it by both starting means (e.g. battery and hydraulic/spring/manual) and know automatic start on blackout
- Regular test records: no-load weekly runs, on-load tests and automatic start/blackout tests
- Emergency switchboard changeover and supply to emergency consumers
- Fuel tank level, quick closing valve condition and operation
- Room clean, ventilation louvres free, starting instructions posted, no stores stored inside
Have ready to show
- Emergency generator test log / PMS records
- Starting instructions posted in the emergency generator room
- Fuel tank sounding/level gauge and quick closing valve
- Blackout test records
- Emergency switchboard and list of emergency consumers
- Starting batteries and charger condition
Avoid
- Officer unable to start the generator by the second means
- Missing or overdue test records
- Ventilation flaps blocked or room used as a store
- Low fuel level or QCV tied open / not resettable