5.2.10 Cargo handling equipment space(s) fixed fire extinguishing system
Rotational 1LNGLPGAsked to: Master, Chief Officer, 2nd / 3rd Officer, Engineer officersWhere: Cargo Control Room, Compressor Room, Main Deck
On gas carriers, do the Master and officers know where the fixed fire extinguishing system for enclosed cargo machinery spaces (compressor and motor rooms) is, its purpose and operation, and is it ready for use with release procedure and instructions displayed at the control stations?
In one lineCO2 protects the compressor/motor rooms; stop machinery, head count, close up, release from the posted station; serviced and checked.
How to answer
- Explain which spaces are protected and where the release controls are
- Walk through the release: stop cargo machinery, head count, close ventilation and doors, open cabinet, release
- Explain safety precautions before entering the CO2 storage room: ventilate, inform, not alone
- Explain servicing and onboard checks
- Explain re-entry only after ventilation and atmosphere testing with BA
What the inspector looks for
- Officers' knowledge of the system (typically CO2) protecting cargo compressor and motor rooms
- Release sequence and pre-discharge alarm
- Instructions posted at release station
- Condition of storage room and cylinders
- Maintenance and service records
Have ready to show
- Release station and posted instructions
- CO2 storage room/cylinders
- Service reports
- PMS records
- Fire control plan
Avoid
- Release instructions missing at the control station
- Officers unclear on head count
- CO2 storage room used for stores
- Annual service by the approved firm overdue