8.6.19 Submerged motor electric cargo pumps
Rotational 2LNGLPGAsked to: Master, Chief Officer, 2nd / 3rd OfficerWhere: Cargo Control Room, Main DeckOnly if it applies to the ship
Where fitted, do the Master and officers know the company procedures for operating submerged electric motor cargo pumps and testing their safety devices and alarms, and have these procedures been followed?
In one lineMegger before use, cool pump and confirm level before starting, test trips, respect the start limit, stop and investigate on low level.
How to answer
- List the protections fitted and explain how they are tested before discharge.
- Describe the insulation resistance check before use and the minimum value you accept.
- Explain the start rules: pump well liquid level and pump cooled down before start, and no more starts per hour than the maker allows.
- Describe actions on low-level alarm and shutdown: reduce rate, prepare stripping, stop the pump, avoid repeated restarts.
- Show the pump log and test records.
What the inspector looks for
- Pump protection devices: low liquid level, low current (dry running), overcurrent, low discharge pressure, start interlocks
- Insulation resistance checks before starting
- Maker's limit on starts per hour and cool-down before start
- Actions on low-level alarm and pump trip
- Records of tests and pump running data
Have ready to show
- Pump maker's manual
- Insulation resistance records
- Trip and alarm test records
- Pump start and running log
- Cargo System Operation Manual
Avoid
- Trips not tested or bypassed
- Repeated restarts beyond the maker's limit
- No insulation checks before use