Unitor — 干粉灭火系统
固定式干粉灭火系统
Manually released dry chemical powder system protecting the cargo tank deck and manifolds of a gas carrier. Two independent centrals each hold powder in a pressure vessel at atmospheric pressure, nitrogen expellant cylinders with regulators, a pneumatically operated main valve and selector valves for the monitors and hose stations. Two monitors cover the cargo manifold; hose stations with 33 m non-kink hoses and powder pistols cover every point on deck from either central. The file covers system description and operation, calculations, data sheets, installation and test procedures and maintenance instructions for monitors, hose reels and centrals.
保养规程
Releasing from a monitor
- Before each loading/discharging, aim the monitors at the manifold in use. 第 4 页
- Open the release cabinet door, open the control cylinder top valve, then the release valve. 第 4 页
- Nitrogen pressurises the powder tank; at about 11 bar the main valve opens and powder flows; the monitor cap pops off. 第 4 页
Releasing from a hose station
- Pull out the hose with pistol close to the fire first. 第 4 页
- Open the cylinder top valve, then the release valve; wait for pressure (about 11 bar) and discharge. 第 4 页Take a firm stand — recoil is possible
技术参数
| Expellant | nitrogen from HP cylinders, regulated to about 14 bar | 第 3 页 |
|---|---|---|
| Main valve opening | sequence valve opens at about 11 bar | 第 4 页 |
| Hose stations | 33 m non-kinkable hose with powder pistol in GRP cabinet | 第 3 页 |
来源:制造商说明书《EM-29 DRY CHEMICAL POWDWE SYSTEM》,共 89 页。页码以原文为准。作业前请核对船上的说明书。
本页为自动翻译。零件号、代码和页码与原文一致。