10.3.2 Electrical distribution system switchboard earth monitoring
Rotational 2ChemicalLNGLPGOilAsked to: Chief Engineer, Engineer officersWhere: Engine Control Room
Do the engineers understand what the insulation (earth fault) monitoring devices on the main and secondary distribution systems are for and how they are set, and are the switchboards free from significant earth faults?
In one lineOur insulation monitors are set per maker for each voltage; earth faults are logged, traced by isolating circuits and cleared promptly.
How to answer
- Explain that ship systems are usually insulated (unearthed) so one earth fault does not trip the supply, but a second fault on another phase can cause a short circuit, so faults must be found quickly
- Describe how the insulation monitor reads and where the alarm set point is taken from (maker's/class settings for each voltage)
- If earth lamps are fitted, explain how to read them: a dim lamp indicates the faulty phase
- Describe tracing an earth fault by isolating circuits one by one with permission and recording the result
- Give the current reading and confirm any fault found is logged and followed up
What the inspector looks for
- Insulation monitors or earth lamps on each system (e.g. 440 V, 220 V, 24 V) working
- Alarm set points correct for the system voltage as per maker/class
- Current readings showing no significant earth fault
- Records of earth faults found, traced and cleared
- Engineers can explain how to trace an earth fault
Have ready to show
- Insulation monitoring meters/earth lamps on main and emergency switchboards
- Maker's settings for alarm points
- Earth fault log / engine log entries
- Defect reports for earth faults
- Insulation resistance test records (megger) for motors
Avoid
- Switchboard showing an earth fault that nobody has reported
- Engineers not understanding how to read the meters or lamps
- Alarm set points changed or alarm disabled
Practise in the interview trainer All questions