5.2.3 Fixed fire detection and fire alarm system
Rotational 1ChemicalLNGLPGOilAsked to: Master, Chief Officer, 2nd / 3rd Officer, Engineer officersWhere: Bridge, Emergency Headquarters., Engine Control Room, Interview - Electrician / ETO
Do the Master and officers understand where the fixed fire detection and alarm system and its panels are, what the system protects and how it works, and is it in good working order with regular inspection, testing and maintenance?
In one lineI can read the panel; all detectors are tested in rotation; isolations are authorised and logged; every alarm is checked at once.
How to answer
- Explain the panel: which zones cover which spaces, how a fire alarm differs from a fault, and where repeaters are (bridge, ECR, fire control station)
- Explain any delay before the general alarm (e.g. on manned bridge acknowledgement) and that it follows approved settings
- Describe the test routine: detectors tested with test gas, smoke or heat in rotation, manual call points tested, all recorded in the PMS
- Describe actions on an alarm: acknowledge, send someone to check the location, inform the Master, fire party on standby, reset only when cause found
- Explain how isolations are authorised, logged with time and reason, and restored when work ends
What the inspector looks for
- Officers able to read the main panel and repeaters: zones, fire, fault and isolation indications
- Any programmed delay before the general alarm and how it is set up
- Rotational detector testing so every head is tested within the company/maker interval
- Control and recording of isolated detectors or zones (e.g. during hot work)
- Outstanding faults or alarms on the panel during the inspection
Have ready to show
- Fire detection main panel and repeaters
- Detector and call point test records
- Detector isolation log / hot work permits
- Detector location plan / zone list
- PMS maintenance history and maker's manual
- Test kits (test gas, heat tester)
Avoid
- Detectors left isolated with no record
- Standing faults accepted as normal
- Officers unable to say which zone covers which space
- Gaps in test records or untested detectors