5.2.5 Machinery space fixed high-expansion foam fire extinguishing system
Rotational 1ChemicalLNGLPGOilAsked to: Master, Chief Officer, 2nd / 3rd Officer, Engineer officersWhere: Emergency Headquarters., Engine Control Room, Engine RoomOnly if it applies to the ship
Where a high-expansion foam system protects the machinery space, are the Master and officers familiar with its location, purpose and operation, and is it in good order, ready for immediate use, with operating instructions clearly posted at the control positions?
In one lineI know the foam tank, control station and spaces covered; release after head count and closing openings; foam analysed in date.
How to answer
- Explain where the foam concentrate tank, pump and control station are and which spaces are covered
- Walk through operation: head count, stop ventilation, close openings, start system from the control station
- Explain maintenance: tank level checks, valve and generator inspections, nozzle/screen checks per PMS
- State when the foam concentrate was last sampled and the result
- Explain why high-expansion foam needs air supply to the generators and the effect on visibility in the space
What the inspector looks for
- Knowledge of the system components: foam concentrate tank, proportioner, generators, release controls
- Operating instructions displayed at control positions
- Foam concentrate quantity and periodic analysis by an approved laboratory
- Maintenance and test records
- Precautions before release (head count, closing ventilation)
Have ready to show
- Foam system control station and posted instructions
- Foam concentrate tank and level gauge
- Foam analysis certificate
- PMS maintenance records
- System diagram
Avoid
- Foam concentrate analysis overdue
- Instructions missing at control position
- Valves or generators corroded or blocked
- Officers unaware of operation
On SeaVint
← 5.2.4 Machinery space fixed carbon dioxide fire extinguishing system5.2.6 Machinery space fixed pressure water-spraying fire extinguishing system →