Insulation resistance: correction to 40 °C

Insulation resistance roughly halves for every 10 °C rise in winding temperature, so readings taken at different temperatures are compared after correction to 40 °C. A falling trend matters more than one reading.

Result
Corrected to 40 °C7.1 MΩ
Recommended minimum (IEEE 43)5 MΩ
Test voltage500 V DC

Above the minimum

How it is calculated

Correction factor Kt = 0.5^((40 − t) / 10), R₄₀ = Kt × Rt. IEEE 43 minimum after 1 minute: 5 MΩ for random-wound and low-voltage windings, 100 MΩ for form-wound windings, kV + 1 MΩ for windings made before 1970. Test voltage: 500 V DC up to 1000 V rated, 500–1000 V up to 2500 V, 1000–2500 V up to 5000 V.

Reference only. The maker's manual and class rules take priority.

Reference table

°CKt
00.062
50.088
100.125
150.177
200.250
250.354
300.500
350.707
401.000
451.414
502.000
552.828
604.000
655.657
708.000
7511.314
8016.000